What size generator do I need?
A real NEC load calculation, not a wattage tally — the same method an electrician uses. Enter your house, add your loads, get a size. No email, no phone number.
Sizing tool
What size generator do you need?
This runs a real NEC load calculation rather than adding up wattages — the same method an electrician uses. Enter your house, add the loads you want backed up, and it will size the unit. Nothing is submitted anywhere.
Your house
Living space plus anything convertible. Exclude a detached garage and open porches.
Kohler ratings are being added; we sell and install both.
Units are rated differently on each fuel — propane usually gives slightly more.
Advanced settings — NEC version, sizing method, elevation(defaults are fine for most homes)
Whichever your local inspector enforces.
Both are permitted. Whichever gives the smaller result is the one to use.
Houston is near sea level. Output drops ~3.5% per 1,000 ft.
From the A/C data plate. Overrides our estimate — nameplate always wins.
Add the loads you want backed up
Server-rendered so it works without scripts and is readable by search engines.
Something not in the list? Enter its nameplate amps and voltage yourself.
Give it a name and a nameplate amp figure above zero.
Appliances & pumps
Kitchen, laundry, water and motor loads
Air conditioning
One kVA per ton of cooling
Heating
Heat pumps, strip heat and thermal storage
EV charging
Level 2 chargers
Selected loads
Nothing added yet. The base calculation already covers general lighting, receptacles and the kitchen and laundry circuits.
How this actually works
Most online generator calculators add up appliance wattages. That is not how sizing is done, and it is why those tools routinely over-recommend. This one runs the NEC dwelling-unit load calculation — the same method your electrician and your inspector use.
It starts from general lighting and receptacle load based on your square footage, adds the required kitchen and laundry circuits, then applies NEC demand factors: not everything in a house runs at once, and the code says by how much you may discount that. Cooking appliances get Table 220.55 treatment, which is why a single 8.5 kW range counts as 6.8 kW rather than 8.5.
Part III or Part IV?
The code permits two methods and you may use either. Part IV (the optional method) lumps general and fixed loads together and takes the first 10 kW at 100% and the remainder at 40%. Part III (the standard method) discounts each category separately. They give different answers on the same house, and the smaller result is the one worth using. The tool defaults to Part IV — switch it in Advanced settings and compare.
Two constraints, not one
Running load is only half the problem. A motor — your A/C compressor, usually — draws several times its running current for the moment it starts, and a generator that comfortably carries your house can still stall on that inrush. So the tool also checks locked-rotor amps against each unit's starting capability and sizes to whichever constraint is tougher. It tells you which one drove the answer.
If you have the A/C data plate to hand, enter the actual LRA in Advanced settings. A real nameplate figure always beats our estimate, even when it is lower.
Fuel and elevation
Generators are rated differently on natural gas and propane — propane usually yields slightly more output — so the fuel you pick changes which unit fits. Elevation derates output by about 3.5% per 1,000 feet; Houston is near sea level, so it rarely matters here, but the field is there if you are sizing somewhere else.
Load management
Tick "load managed" on a big intermittent load like an A/C or an EV charger and it drops out of the NEC calculation — that is what a load-management module buys you, and it can drop you a whole generator size. It still counts toward starting current, because a module sheds a load after it is running, not during the inrush.
What it cannot tell you
This is an estimate for getting you into the right bracket, not a stamped load calculation. It does not know your actual panel, your service size, whether your gas line can carry the demand, or where a unit can legally sit on your lot. The default wattages are typical figures — override them with your nameplate values wherever you have them.
Commercial buildings need a proper load study rather than this — see commercial generators.